1, the overcurrent (OC) Inverter over-current alarm is the most frequent phenomenon. 1.1 phenomenon      (1) restarts, a liter of speed on the trip. This is very serious over-current phenomenon. Main reasons: the load short circuit, mechanical parts are stuck; inverter module damage; motor torque is too small to cause such phenomena.      (2) on the power on the jump, a phenomenon generally can not be reset, for two main reasons: module bad, bad driver circuit, the current detection circuit bad.      (3) does not restart immediately when the trip but when accelerating, for two main reasons: the acceleration time is set too short, the current limit is set too small, the torque compensation (V / F) set higher.   2, overvoltage (OU)      Overvoltage alarm usually occurs during idle time, mainly due to the deceleration time is too short or braking resistor and braking unit in question. ...